Backflow Prevention Requirements for Commercial Kitchens and Restaurants
Commercial kitchens and restaurants require a reliable water supply for preparing food and drinks and other kitchen activities. Cross-connections and specialised equipment used in commercial kitchen and restaurant plumbing systems create a potential for contamination of the water supply.
This is where backflow prevention comes into play.
Depending on the nature of the business, a restaurant or café may require an appropriate backflow prevention device to protect the potable water supply from contamination due to back-siphonage or back-pressure.
All food business operators should understand backflow prevention and its implications for their business, to stay compliant with plumbing requirements, protect public health and avoid disruption to trading.
This article explains backflow prevention and devices, the rationale behind testing, and how plumbing services help fulfil backflow prevention requirements.
What Is Backflow Prevention in Commercial Kitchens?
Backflow is the undesirable condition of water flowing in the opposite direction in a plumbing system. In the public water supply system, water is meant to flow from the water supply to the outlets. Contaminated or potentially contaminated water should not flow into the public drinking water supply.
There are two main conditions that result in backflow:
- +Back-siphonage: A drop in pressure in the water supply (for example, from a main break or high demand) draws water backwards from the connected system into the drinking water supply.
- +Back-pressure: Pressure in the connected system becomes greater than the pressure in the drinking water supply, pushing water backward through the system.
In commercial kitchens, cross-connections may occur between drinking water supplies and equipment or systems that contain cleaning chemicals, wastewater, food residues or other contaminants.
A correctly selected backflow prevention device provides protection against back-siphonage and back-pressure and addresses the risk of potential backflow.
Why Is Backflow Prevention Important for Restaurants and Commercial Kitchens?
A commercial food premises uses water for a variety of purposes, and not all plumbing connections have the same potential level of contamination.
A commercial food premises may have numerous plumbing connections serving sinks, dishwashers, equipment used for cleaning, food preparation areas, and other specialised systems.
In the absence of appropriate cross-connection controls, contaminated water may flow into the drinking water system.
What are some of the primary reasons for the importance of backflow prevention?
1. Protect Drinking Water Quality
In a commercial kitchen, food, cleaning agents, and wastewater may come in contact with the drinking water supply. A backflow prevention device helps reduce the risk of contamination to the drinking water supply.
2. Meet Plumbing and Water Authority Requirements
Food businesses are required to adhere to applicable plumbing regulations, the Plumbing Code of Australia, Australian Standards and their water authority’s connection requirements.
In Sydney, a business is required to adhere to the backflow prevention and testing requirements of Sydney Water.
3. Protect Employees and Customers
A backflow prevention device, properly designed and installed, helps protect the water supply used by employees of the food premises and customers.
4. Avoid Plumbing Compliance Problems
If devices are not properly installed, registered or maintained, compliance problems can follow. Keeping the devices in good working order helps businesses manage their plumbing responsibilities.
5. Support Uninterrupted Business Operations
Problems with the water supply can disrupt food preparation, dishwashing and other activities in a restaurant. Preventive plumbing maintenance can help identify problems and allow corrective action before they become an emergency.
What Backflow Prevention Requirements Apply to Commercial Kitchens in Sydney?
The backflow prevention requirements depend on the property’s hazard rating, the configuration of the plumbing, the equipment connected to the plumbing, and the requirements of the water authority.
Sydney Water requires commercial and industrial properties to have their cross-connection hazards assessed by an accredited backflow plumber.
Depending on the assessment, the level of protection may vary.
The general classifications of hazards are:
- +Low — Description: A condition that may cause a nuisance but not endanger health or safety; Protection: Appropriate non-testable containment protection
- +Medium — Description: A condition that may endanger health; Protection: A testable device such as a double check valve
- +High — Description: A condition that may cause serious injury or death; Protection: Appropriate high-hazard protection
Rather than assuming which backflow prevention device a restaurant needs, an assessment should be carried out to determine the level of protection required.
Types of Backflow Prevention Devices Used in Commercial Premises
There are different types of backflow prevention devices based on the level of contamination risk. The selection of the appropriate device is based on the assessment of the hazard rating and the relevant requirements for installation.
1. Reduced Pressure Zone (RPZ) Device
A reduced pressure zone device is designed to provide a high level of backflow protection. It is used to protect against a high-level hazard cross-connection.
Some key features are:
- +It is designed to provide protection against potential cross-connections in high hazard situations.
- +It uses a reduced pressure zone to provide protection against backflow.
- +It has test points to facilitate performance testing.
- +Suitable provision for drainage and maintenance is required.
- +It must be tested by a plumber who is accredited to carry out such tests.
2. Double Check Valve Assembly
A double check valve assembly is made up of two independent check valves to prevent reverse flow of water.
It is used to provide backflow protection in medium hazard situations where it is required by the relevant standards and the water authority.
It has the following features:
- +It provides protection against back-pressure and back-siphonage in its approved application.
- +It has test points to facilitate performance testing.
- +It requires periodic testing and maintenance.
3. Registered Air Gap
An air gap provides a physical separation between a drinking water outlet and a potentially contaminated water source. When correctly designed and installed, it helps to prevent contaminated water from flowing back into the drinking water supply. An air gap may be used to provide protection for some high-hazard situations subject to the relevant design and registration requirements.
4. Non-Testable Backflow Prevention Devices
Non-testable backflow prevention devices are used to protect some low-hazard connections.
These devices offer a sufficient level of protection for the application and are exempt from the same level of testing as testable assemblies.
The appropriate device must be determined in accordance with the relevant hazard assessment and water authority requirements.
Backflow Prevention and Grease Trap Requirements
Many food businesses use grease traps as part of wastewater management.
During the normal course of food preparation and cleaning activities, restaurants and food businesses produce wastewater that contains fats, oils and grease.
Grease traps intercept these materials prior to the wastewater entering the sewerage system.
A backflow prevention device and grease trap serve different functions.
- +A grease trap is used to intercept fats, oils and grease from commercial wastewater.
- +A backflow prevention device is used to prevent the backflow of contaminated water into the drinking water supply.
Both may be required of a food business.
In its guidance for food businesses, Sydney Water states that most food premises need a correctly sized grease trap and other pre-treatment equipment, such as bucket traps, as part of an appropriate pre-treatment system.
Sydney Water also requires food businesses to have backflow prevention for the property, and taps located near the grease trap (within about 5 metres) need appropriate backflow protection.
These requirements should be verified for the specific premises and the most current Sydney Water guidance.
Does a Restaurant Need Annual Backflow Testing?
Where a food premises has a testable backflow prevention containment device in accordance with Sydney Water requirements, an accredited backflow plumber must test the device annually.
A device is tested to make sure it is functioning and providing the required protection.
In Sydney, the accredited plumber must also submit the test results to Sydney Water within 2 days.
Annual testing of a backflow prevention device typically consists of:
1. Inspecting the Existing Device
The plumber verifies the condition of the device, determines if it is accessible, and looks for signs of damage or deterioration.
2. Checking the Device Identification
The plumber confirms device details and relevant registration information.
3. Conducting Performance Tests
Using approved and calibrated testing equipment, the accredited plumber carries out tests to determine if the device performs in accordance with the requirements.
4. Identifying Defects
If a test fails, the plumber determines the reason for the test failure and recommends corrective action.
5. Submitting Test Results
The test results are forwarded to the water authority in a timely manner.
6. Recording the Next Testing Date
Accurately maintaining a compliance register helps business owners determine when the next test is due and prevents missed test requirements.
Common Backflow Prevention Problems in Commercial Kitchens
There are several performance and compliance concerns that can affect backflow prevention devices. These include:
Incorrect Device Selection
If a device is installed that does not provide the required level of protection, the premises is unprotected.
The device is chosen based on the assessment of the site’s potential hazard.
Failed Annual Testing
A testable device may fail due to worn or damaged components.
Devices that fail testing must be repaired or replaced.
Missing Registration or Documentation
Failure to fully and accurately register devices or to maintain sufficient records of testing can create problems when demonstrating compliance.
It is the responsibility of the property owner or occupier to accurately record and retain records of the location and test results of the backflow prevention devices on the property.
Poor Accessibility
Devices installed in hard-to-reach places can make routine testing and inspections difficult.
Backflow prevention devices should be designed, installed and located to facilitate testing and maintenance.
Lack of Preventative Maintenance
Commercial kitchens have a significant amount of water flow, usage and equipment operation. When ongoing plumbing maintenance is neglected, equipment problems and leaks can be compounded, and cross-connection compliance issues can also arise.
Early identification of these problems can help alleviate these issues; therefore, a scheduled maintenance programme is beneficial.
Backflow Prevention Checklist for Restaurant Owners
Restaurant owners and managers can use this checklist to evaluate plumbing arrangements in their commercial kitchens.
- +Arrange an on-site assessment of your plumbing arrangement by a qualified and licensed backflow plumber.
- +Confirm your property’s cross-connection hazard level.
- +Make sure required backflow prevention devices are installed.
- +Make sure testable backflow prevention devices are registered and their locations recorded.
- +Maintain records of device location and identification.
- +Have devices that require annual testing tested, with the results forwarded to the water authority.
- +Check that grease traps, pre-treatment and other devices meet the local authority's requirements.
- +Ensure devices are located in a manner that allows maintenance and inspection.
- +Address issues associated with device failure, plumbing defects and cross-connection.
These measures should help hospitality businesses manage their plumbing requirements and provide a safer water supply.
Why Choose Local Plumbing Patrol for Commercial Backflow Prevention in Sydney?
Managing multiple backflow prevention devices and requirements for annual testing can be challenging for businesses in the café and restaurant sector.
Local Plumbing Patrol offers TMV and backflow prevention services in Sydney.
Our backflow prevention services include:
- +Installation of backflow prevention devices.
- +Conducting annual backflow tests.
- +Replacing/Repairing backflow prevention devices.
- +Preparing and submitting compliance documentation to Sydney Water.
- +Maintaining compliance registers for backflow prevention devices.
- +Ongoing plumbing maintenance for businesses.
Our process includes assessing your device and making recommendations for testing and maintenance.
Local Plumbing Patrol services the backflow prevention needs of Sydney’s restaurant and food industry.
Contact Local Plumbing Patrol
Phone: (02) 9606 4913 | Email: info@localplumbingpatrol.com.au
For commercial backflow prevention and testing, contact Local Plumbing Patrol for a quote.
Conclusion
Commercial kitchen plumbing includes backflow prevention to prevent contamination of drinking water due to the reversal of water flow.
Backflow prevention may include a backflow prevention device, depending on the Sydney Water hazard rating of your business and the types of plumbing connections.
An understanding of local codes and training in backflow prevention can help food businesses manage these requirements. This includes the selection of the right backflow prevention device and annual testing.
Local Plumbing Patrol can assist if your commercial kitchen or restaurant requires backflow prevention systems installed, tested or repaired. We offer commercial plumbing services across Sydney.
Frequently Asked Questions
1. Is backflow prevention required in commercial kitchens?
All commercial properties in Sydney must have cross-connection control. The protection required depends on the site’s hazard rating and plumbing configuration, as well as the water authority’s requirements. Sydney Water requires that commercial properties have their hazards assessed by an accredited backflow plumber.
2. How often should restaurant backflow prevention devices be tested?
According to Sydney Water, testable backflow prevention devices must be tested annually, and the results must be submitted by an accredited backflow plumber within 2 days.
3. What type of backflow prevention device does a restaurant need?
The chosen option depends on the assessed hazard rating. These may include a double check valve assembly, a reduced pressure zone device or a registered air gap. An accredited backflow plumber assesses the premises and determines the required level of protection.
4. Is a grease trap the same as a backflow prevention device?
A grease trap is not a backflow prevention device. A backflow prevention device is used to stop backflow, which is the undesirable reverse flow of potentially contaminated water into the drinking water supply. A commercial food premises may require both a grease trap and a backflow prevention device.
5. Who can install and test backflow prevention devices in Sydney?
A licensed plumber can install a backflow containment device. An appropriately accredited backflow plumber must carry out assessment, commissioning, testing and registration in accordance with Sydney Water requirements.